# TR Pro.

![TR Pro](https://ke.elvorka.com/assets/optimized/46a9d9acb1b4d427-1560-q92.webp)

Low-voltage battery

# TR Pro.

LFP battery storage in a wall-mounted format, with three specified models and an IP66 enclosure. Pair with a compatible external inverter.

INVERTER  Compatible external inverter required

ENCLOSURE  IP66

NOMINAL ENERGY  10.24 / 16.076 kWh

BATTERY VOLTAGE  51.2 V nominal DC

[Start your project ↗](https://ke.elvorka.com/en/#enquiry)

## Specifications

| Model / configuration | Energy (kWh) | Rated DC (kW) |
| --- | --- | --- |
| TR6000WX-Pro | 10.24 | 10 |
| TR8500WX-Pro | 16.076 | 10 |
| TR8500WX-ProU | 16.076 | 10 |

Self-heating is optional. Power ratings are battery-side DC; actual AC output depends on the selected inverter.

| Model | Dimensions (mm) | Approx. kg |
| --- | --- | --- |
| TR6000WX-Pro | 802 × 620 × 179 / H × L × D | 95 |
| TR8500WX-Pro | 822 × 500 × 250 / H × L × D | 115.5 |
| TR8500WX-ProU | 872 × 500 × 250 / H × L × D | 120 |

Communication: RS485 / RS232 / CAN; Wi-Fi / Bluetooth
Temperature: Charge 0 to 55 °C; discharge −20 to 60 °C

## A highland home and a coastal home have different storage needs.

Kenya spans temperate highlands, hotter humid coastal areas and arid or semi-arid lowlands. Plan a useful energy reserve around your household loads, then choose the battery format and a protected equipment space for your particular location.

Temperature:  Charge 0 to 55 °C; discharge −20 to 60 °C

ENCLOSURE  IP66

01

### Highland home with a dedicated service room

For a home office, refrigeration and selected lights, a dry indoor utility space can keep the system close to the circuits it serves and leave straightforward service access.

An EU integrated system brings battery and inverter together. A TR Pro 51.2 V battery can instead work with a confirmed compatible existing inverter; size energy for the hours you choose and retain the selected model’s clearances.

Which circuits and backup hours would you like to plan for?

- What are the minimum and maximum temperatures inside the proposed room?

02

### Coastal home with a sheltered equipment area

The hotter, more humid coast calls for attention to a room’s airflow, rain exposure and coastal air. A protected service room gives refrigeration, fans and connectivity a practical installation setting.

TR Pro provides compact 51.2 V storage; HP Ultra provides a modular high-voltage format. Both list IP66. Select the architecture to match the inverter, with shelter and environmental conditions reviewed for the exact model.

Can rain, condensation, wash water or coastal air reach the equipment?

- Is the inverter a 51.2 V or high-voltage battery system?

03

### Warmer inland site with more dust exposure

In a warmer or dusty inland location, an enclosed dry equipment area with clear airflow helps keep the battery installation accessible and protected from everyday activity.

Choose wall or floor-mounted storage to suit available service space. Review the actual enclosure option and room temperature: standard TR and HP K list IP20 with IP54 optional, while HP Ultra needs its temperature range confirmed for the selected configuration.

How will dust ingress and the room’s heat be managed?

- Can cooling paths, fixing points and power/communication routes remain clear?

Specifications

- Pair energy and power: kWh helps plan duration, while the compatible inverter’s kW rating, battery limits and starting-load capability determine which circuits can run together.

- TR Pro lists charging at 0 to 55 °C and discharging at −20 to 60 °C; EU lists charging at 0 to 55 °C and discharging at −20 to 55 °C. HP Ultra’s temperature limits require configuration-specific confirmation. Check the room, rather than a national temperature label.

- Specify shelter and the exact enclosure. IP66 does not itself establish flood, condensation or coastal-corrosion suitability; source temperature limits do not guarantee full output at every temperature.

PRODUCT DETAIL / ORIGINAL LITERATURE

## Every side. Every connection.

The panel illustrates one wheeled representative housing rather than proving every Pro SKU has the same lower body or port placement. Roller is a wheel. Main Circuit Breaker and Battery Switch are separate source labels. Full embedded switch-photo content beyond the printed crop is not promoted to new interface claims.

[![Connection-side terminal labels](https://ke.elvorka.com/assets/product-details/tr-pro-terminal-labels.png)](https://ke.elvorka.com/assets/product-details/tr-pro-terminal-labels.png)

Connection-side terminal labels  Battery terminals, switch, Wi-Fi antenna and communication ports on the cabinet side.

[![Main breaker and folding handle](https://ke.elvorka.com/assets/product-details/tr-pro-breaker-side-labels.png)](https://ke.elvorka.com/assets/product-details/tr-pro-breaker-side-labels.png)

Main breaker and folding handle  Main circuit breaker and folding handle on the illustrated cabinet side.

[![Original connection-side three-quarter view](https://ke.elvorka.com/assets/product-details/tr-pro-connection-side.png)](https://ke.elvorka.com/assets/product-details/tr-pro-connection-side.png)

Original connection-side three-quarter view  Connection-side view of the cabinet, battery terminals and folding handle.

[![Original narrow side profile](https://ke.elvorka.com/assets/product-details/tr-pro-slim-side-profile.png)](https://ke.elvorka.com/assets/product-details/tr-pro-slim-side-profile.png)

Original narrow side profile  Narrow side profile of the illustrated cabinet.

[![Original circuit-switch photograph](https://ke.elvorka.com/assets/product-details/tr-pro-switch-original-photo.png)](https://ke.elvorka.com/assets/product-details/tr-pro-switch-original-photo.png)

Original circuit-switch photograph  Circuit-control switch with ON and OFF position markings.

### Know your interfaces.

#### Power connections

Positive battery terminal  Positive DC battery terminal identified on the connection side.

Negative battery terminal  Negative DC battery terminal identified on the connection side.

#### Communication

RS485  RS485 interface named in the source; pinout and compatible device list are not provided.

Wi-Fi antenna  Wi-Fi antenna identified by the original arrow.

CAN  CAN communication interface named in the source; protocol version and pinout are not specified.

RS232  RS232 communication interface named in the source; pinout is not specified.

COM1  Port named COM1; this page does not explicitly define its role or wiring.

COM0  Port named COM0; this page does not explicitly define its role or wiring.

#### Controls & indicators

Breathing light  Front status-light strip identified as a breathing light. Colour meanings and operating logic are not specified.

Main circuit breaker  Main circuit breaker identified by the original arrow. Trip ratings and wiring are not provided here.

Battery switch  Battery switch separately named in the connection-side callout; do not merge this label with Main Circuit Breaker without a model-specific manual.

#### Structure & mounting

Wall-mounted bracket  Mechanical wall-mounting bracket; not an electrical interface.

Rollers  Wheels shown on the representative housing. The label is mechanical and is not a connector or bottom communication port.

Folding handle  Mechanical folding handle; not an electrical connector.

Source: Residential ESS brochure · PDF page 4 · printed pages 7-8

---